Add to Cart
ELECMAN ® ANSI C80.3 UL797 Gi Electrical Metallic Tubing 1" EMT Pipe EMT Tube
Application
ELECMAN® UL797 EMT conduit is produced in normal trade sizes from 1/2" to 4". EMT is produced in standard lengths of 10’ (3.05 m), and can also be customized according to customer requirements. EMT conduit is used to provide long-lasting external protection for conductors and cables. EMT is installed by use of set screw or compression-type couplings and connectors.
Features
Certifications and Compliances
ELECMAN® UL797 carbon steel electrical metallic tubing (EMT conduit) in accordance with the National Electrical Code (NEC). Electrical metallic tubing shall be carbon steel, electrically welded, galvanized and produced to the following specifications:
Specification Data
ELECMAN ® UL797 carbon steel electrical metallic tubing (EMT) is listed to UL Safety Standard 797 and manufactured in accordance with ANSI C80.3. details shall accord with Table 1.
Table 1 | |||||||
CAT # | Trade size | Outside Diameter | Wall Thickness | Length | |||
Inch | mm | Inch | mm | Feet | mm | ||
EMT050 | 1/2" | 0.706 | 17.93 | 0.042 | 1.07 | 10 | 3050 |
EMT075 | 3/4" | 0.922 | 23.42 | 0.049 | 1.25 | 10 | 3050 |
EMT100 | 1" | 1.163 | 29.54 | 0.057 | 1.45 | 10 | 3050 |
EMT125 | 1-1/4" | 1.510 | 38.35 | 0.065 | 1.65 | 10 | 3050 |
EMT150 | 1-1/2" | 1.740 | 44.20 | 0.065 | 1.65 | 10 | 3050 |
EMT200 | 2" | 2.197 | 55.80 | 0.065 | 1.65 | 10 | 3050 |
EMT250 | 2-1/2" | 2.875 | 73.03 | 0.072 | 1.83 | 10 | 3050 |
EMT300 | 3" | 3.500 | 88.90 | 0.072 | 1.83 | 10 | 3050 |
EMT350 | 3-1/2" | 4.000 | 101.60 | 0.083 | 2.11 | 10 | 3050 |
EMT400 | 4" | 4.500 | 114.30 | 0.083 | 2.11 | 10 | 3050 |
Notes: Applicable tolerance | |||||||
Length: 10ft±1/4in. 3050mm ±6.35mm. | |||||||
Outside Diameter: 1/2" to 2" ±0.005in.(16mm to 53mm ±0.13mm). | |||||||
2-1/2" ±0.010in. (63mm ±0.25mm). | |||||||
3" ±0.015in. (78 ±0.38mm). | |||||||
3-1/2" to 4" ±0.020in. (91mm to 103mm ±0.51mm) |
Raw Material
ELECMAN ® Electrical metallic tubing (EMT) is produced from Carbon structural steel (Q195).
Chemical Composition
Steel type and chemical composition (melting analysis) shall accord with Table 2.
Table 2 | |||||||
Type | Grade | Chemical composition,% | Deoxidization Method | ||||
C | Mn | Si | S | P | |||
Maximum | |||||||
Q195 | - | 0.06-0.12 | 0.25-0.50 | 0.3 | 0.05 | 0.045 | F,b,Z |
Manufacturing Process
ELECMAN ® Electrical metallic tubing (EMT) is manufactured according to following production process:
Quality Control
Every ELECMAN people know deeply the core value of ELECMAN is to provide high quality products to customers, that is why ELECMAN QC departments have very strict quality controlling process, from raw material to products, ELECMAN QC department supervise every process, make sure every process follow the standard, for EMT conduit, QC department need to inspect the dimensions, welding line, zinc coatings and bending feature.
Packing Information
EMT conduits are packed in bundles with woven bag, we also can put customers' sticker on pipes, on woven bag, we will put a big sticker with detailed information for customers to distinguish different sizes. for regular packing information, please check the Table 3.
Table 3 | ||||||
CAT # | Trade size | O.D. | Thickness | Weight | Packing | |
mm | mm | kgs | pcs/small bundle | small bundle/big bundle | ||
EMT050 | 1/2" | 17.93 | 1.07 | 1.357 | 20 | 30 |
EMT075 | 3/4" | 23.42 | 1.25 | 2.069 | 15 | 20 |
EMT100 | 1" | 29.54 | 1.45 | 3.063 | 10 | 20 |
EMT125 | 1-1/4" | 38.35 | 1.65 | 4.555 | 5 | 10 |
EMT150 | 1-1/2" | 44.20 | 1.65 | 5.281 | 5 | 10 |
EMT200 | 2" | 55.80 | 1.65 | 6.720 | 5 | 10 |
EMT250 | 2-1/2" | 73.03 | 1.83 | 9.800 | 2 | 20 |
EMT300 | 3" | 88.90 | 1.83 | 11.980 | 1 | 30 |
EMT350 | 3-1/2" | 101.60 | 2.11 | 15.680 | 1 | 30 |
EMT400 | 4" | 114.30 | 2.11 | 17.800 | 1 | 30 |
Note: Can be packaged according to the customer's packing requirements |